Description
10 hp variable frequency drive, three phase 220V /440V /480V ±15%, IP20 enclosure.
Specification:
| Basics | Model | GK3000-4T0075G/ GK3000-2T0075G |
| Capacity | 10 hp (7.5 kW) | |
| Shipping weight | 5 kg | |
| Dimension | 272*172*182 mm for GK3000-4T0075G/ 330*200*200 for GK3000-2T0075G | |
| I/O Feature | Rated current | 17A at 380V ~ 480V, 32A at 220V ~ 240V |
| Input voltage | 3 phase 220V /440V /480V AC ±15% (Optional) | |
| Input frequency | 50Hz/ 60Hz | |
| Output voltage | 3 phase AC 0~input voltage | |
| Output frequency | 0Hz~1000Hz | |
| Over load capacity | 150% of rated current for 1 minute, 180% of rated current for 3 seconds | |
| Control Feature | Control mode | V/F control; Sensorless vector control; |
| Communication | RS485 | |
| Speed regulation | 1:100 | |
| Start torque | 150% of rating torque at 1 Hz | |
| Speed control accuracy | ≤±0.5% of rating synchronous speed | |
| Frequency precision | Digital setting: max frequency x± 0.01%; Analog setting: max frequency x± 0.2% |
|
| Frequency resolution | Analog setting: 0.1% of max frequency; Digital setting: 0.01Hz |
|
| Torque boost | Automatic torque boost, manual torque boost 0.1%~30.0% | |
| Interior PID controller | Be convenient to make closed-loop system | |
| Automatic energy save running | Optimize V/F curve automatically based on the load to realize power save running | |
| Automatic voltage regulation (AVR) | Can keep constant output voltage when power source voltage varies. | |
| Automatic current limiting | Limit running current automatically to avoid frequent over-current which will cause trip | |
| Environment | Enclosure rating | IP 20 |
| Temperature | –10℃~ +40℃; VFD will be derated if ambient temperature exceed 40℃; each rise 1℃, the derate will be 5% | |
| Humidity | 5%-95%, without condensation | |
| Altitude | ≤1000m; VFD will be derated if above 1000m | |
| Impingement and oscillation | Normal running:<5.9m/s2 (0.6g); Transportation:<15m/s2 (1.5g) | |
| Store environment | –20℃~ +60℃; no dust, no corrosive gas, no direct sunlight |
Note: ATO VFD Cannot be used as a power source, it Can only be directly connected to an induction motor to control the motor speed.
Tips: Variable frequency drive fault dynamic test method
The dynamic test can only be proceeding after the static test result is normal. Dynamic testing must note the following issues:
- Before powering, the input voltage must be confirmed. If connect 380V power supply into 220V VFD, the VFD will be burned.
- Check all the connections of the VFD to be correct connected and fastened. Improper connection may lead to failure, or seriously, to be burned.
- After power on, check the failure display content, and initially determine the reasons.
- If the fault is not displayed, first check whether the parameters are abnormal, and then reset the parameters, and start VFD to test U/V/W three-phase output voltage under no-load situation.
- When the output voltage is normal and three-phase equilibrium, start load test. And it’s best to start full load test.